I once spent over a year debugging a furnace. It would run fine, except every now and then on it would just refuse to turn on for a day or two. Eventually noticed it was only rainy days, and was due to it thinking the exhaust was blocked because there wasn't enough pressure differential between input air and exhaust.
Turned out the installer had failed to put in the high altitude kit which told it to expect a smaller pressure differential. Mostly it was fine, but on rainy days with low barometric pressure, the difference would drop below threshold. But I had to be home for enough rainy days to figure it out.